1. Servo Memory Table Definition​

If a function address uses two bytes of data, the low byte is at the earlier address, and the high byte is at the later address.

1.1 Version Information​

Address DECAddress HEXFunction NameBytesInitial ValuePermissionValueUnitDescription
00x00Firmware major version number1-Read-only---
10x01Firmware minor version number1-Read-only---
20x02END10Read-only--0 indicates little-endian storage structure
30x03Servo major version number1-Read-only---
40x04Servo minor version number1-Read-only---

1.2 EPROM Configuration​

Address DECAddress HEXFunctionBytesInitial ValuePermissionValueUnitDescription
50x05Servo ID11Read/write0 - 253NumberUnique primary ID identifier in the bus
60x06Baud rate10Read/write0 - 7None0 - 7 respectively represent baud rates: 1000000(0), 500000(1), 250000(2), 128000(3), 115200(4), 76800(5), 57600(6), 38400(7)
70x07Reserved address1-Read/write---
80x08Response status level11Read/write0 - 1None0: except for read commands and the PING command, other commands do not return a response packet; 1: return a response packet for all commands
90x09Minimum angle limit20Read/write0 - 40940.087 degreeIn multi-turn absolute position control, this value is 0
110x0BMaximum angle limit24095Read/write1 - 40950.087 degreeIn multi-turn absolute position control, this value is 0
130x0DMaximum temperature upper limit170Read/write0 - 100°C-
140x0EMaximum input voltage1-Read/write0 - 2540.1V-
150x0FMinimum input voltage140Read/write0 - 2540.1V-
160x10Maximum torque21000Read/write0 - 10000.1%Assigned to address 48 torque limit at power-on
180x12Phase1-Read/write0 - 254NoneSpecial function byte; do not modify unless specifically required
190x13Unload condition1-Read/write0 - 254NoneSetting the corresponding bit to 1 enables the corresponding protection; setting the corresponding bit to 0 disables the corresponding protection
200x14LED alarm condition1-Read/write0 - 254NoneSetting the corresponding bit to 1 enables the flashing light alarm; setting the corresponding bit to 0 disables the flashing light alarm
210x15Position loop P proportional coefficient1-Read/write0 - 254NoneProportional coefficient controlling the motor (1/4)
220x16Position loop D derivative coefficient1-Read/write0 - 254NoneDerivative coefficient controlling the motor (1/8)
230x17Position loop I integral coefficient10Read/write0 - 254NoneIntegral coefficient controlling the motor
240x18Minimum starting torque1-Read/write0 - 2540.1%Set the servo's minimum output starting torque
250x19Integral limit value10Read/write0 - 254NoneMaximum integral value = integral limit value * 4; 0 indicates disabling the integral limit function; effective in position mode 0 and mode 4
260x1APositive dead zone11Read/write0 - 160.087 degreeThe minimum unit is one minimum resolution angle
270x1BNegative dead zone11Read/write0 - 160.087 degreeThe minimum unit is one minimum resolution angle
280x1CProtection current2511Read/write0 - 20476.5mAMaximum settable current is 500 * 6.5mA = 3250mA
300x1EAngle resolution11Read/write1 - 128NoneAmplification factor for the sensor's minimum resolution angle
310x1FPosition offset20Read/write0 - 81910.087 degree0 - 2047 represents 0 - 2047; 2048 - 4095 represents 0 to -2047; 4096 - 6143 represents 2048 - 4095; 6144 - 8191 represents -2048 to -4095 (representing offset positions -4095 - 4095)
330x21Operating mode10Read/write0 - 3None0: position servo mode; 1: motor constant speed mode; 2: PWM open-loop speed control mode; 3: stepper mode
340x22Holding torque120Read/write0 - 2541%Output torque after entering overload protection; for example, setting 20 means 20% of the maximum torque
350x23Protection time1200Read/write0 - 25410msThe timing duration during which the current load output exceeds the overload torque and is maintained; for example, setting 200 means 2 seconds, with a maximum settable value of 2.5 seconds
360x24Overload torque180Read/write0 - 2541%The maximum torque threshold that triggers the start of the overload protection timing; for example, setting 80 means 80% of the maximum torque
370x25Speed closed-loop P proportional coefficient1-Read/write0 - 254NoneIn motor constant speed mode (mode 1), the speed loop proportional coefficient
380x26Overcurrent protection time1200Read/write0 - 25410msMaximum settable value 254 * 10ms = 2540ms
390x27Speed closed-loop I integral coefficient1-Read/write0 - 254NoneIn motor constant speed mode (mode 1), the speed loop integral coefficient

1.3 SRAM Control​

Address DECAddress HEXFunction NameBytesInitial ValuePermissionValueUnitDescription
400x28Torque switch10Read/write0 - 2, 128NoneWrite 0: disable torque output; write 1: enable torque output; write 2: damping output (torque limit (48) can control the damping force magnitude); write 128: calibrate any current position to 2048
410x29Acceleration10Read/write0 - 2548.7 degree/s²Servo running acceleration/deceleration; 0 indicates maximum acceleration
420x2ATarget position20Read/write-32767 - 327670.087 degreeAbsolute position control method; the maximum corresponds to the maximum effective angle; BIT15 is the direction bit
440x2CPWM open-loop speed21000Read/write0 - 10000.1%Effective in PWM open-loop speed control mode; BIT10 is the direction bit
460x2ERunning speed2Servo factory default maximum speedRead/write-32767 - 327670.732 RPM / 0.0146 RPMControl the motor's maximum running speed; BIT15 is the direction bit; speed 0 by default indicates the maximum speed, and can be set through the phase so that 0 indicates stop; the speed unit can be set through the phase, with two units 0.732RPM / 0.0146RPM; when the speed unit is set to 0.0146RPM, its precision is also 0.732RPM. 0.732RPM = 50 steps/second; 0.0146 RPM = steps/second
480x30Torque limit2Maximum torque (16), default 1000Read/write0 - 10000.1%Users can modify this value through programming to control the stall torque output
50 - 540x32 - 0x36Undefined1-Read/write---
550x37Lock flag11Read/write0 - 1NoneWrite 0 to disable the write lock, and values written to EPROM addresses are saved after power-off; write 1 to enable the write lock, and values written to EPROM addresses are not saved after power-off

1.4 SRAM Feedback​

Address DECAddress HEXFunction NameBytesInitial ValuePermissionValueUnitDescription
560x38Current position2-Read-only-0.087 degreeFeedback of the servo's current absolute position; BIT15 is the direction bit; in stepper mode 3, returns the step difference between the current position and the target position; BIT15 is the direction bit
580x3ACurrent speed2-Read-only-0.732 RPM/0.0146 RPMFeedback of the current motor rotation speed; the speed unit is set according to the phase; BIT15 is the direction bit
600x3CCurrent load2-Read-only-0.1%Current control output voltage duty cycle driving the motor; BIT10 is the direction bit
620x3ECurrent voltage1-Read-only-0.1VCurrent servo operating voltage
630x3FCurrent temperature1-Read-only-°CCurrent internal operating temperature of the servo
640x40Asynchronous write flag10Read-only-NoneFlag bit when using asynchronous write commands
650x41Servo status10Read-only-NoneSetting the corresponding bit to 1 indicates that the corresponding error has occurred
660x42Moving flag10Read-only-NoneThe flag is 1 when the servo is moving, and 0 when the servo reaches the target and stops; it remains 0 when the servo does not update the target position
670x43Target position20Read-only-0.087 degreeCurrent target position
690x45Current current2-Read-only-6.5 mAFeedback of the current motor phase current
710x47Undefined2-Read-only---

2. Special Byte Explanation​

2.1 Servo Status​

Byte BitBIT7BIT6BIT5BIT4BIT3BIT2BIT1BIT0
Bit Weight1286432168421
Address 65----Load status--Current statusTemperature statusMagnetic encoder statusVoltage status
 ----(0) Load normal--(0) Current normal(0) Temperature normal(0) Magnetic encoder normal(0) Voltage normal
----(1) Load overload--(1) Current overcurrent(1) Temperature overheating(1) Magnetic encoder abnormal(1) Overvoltage/undervoltage
info

If multiple statuses occur at the same time, the servo status value is the sum of the individual bit values. For example: overvoltage/undervoltage and servo overheating give a servo status value of 4+1=5.

2.2 LED Alarm Condition​

Byte BitBIT7BIT6BIT5BIT4BIT3BIT2BIT1BIT0
Bit Weight1286432168421
Address 20----Load overload alarm--Overcurrent alarmOverheating alarmMagnetic encoder alarmVoltage alarm
 ----(0) Disable load overload alarm--(0) Disable overcurrent alarm(0) Disable overheating alarm(0) Disable magnetic encoder alarm(0) Disable voltage alarm
----(1) Enable load overload alarm--(1) Enable overcurrent alarm(1) Enable overheating alarm(1) Enable magnetic encoder alarm(1) Enable voltage alarm
info

If multiple bits are set at the same time, the servo's LED alarm condition value is the sum of the individual bit values. For example: enabling both the voltage alarm and the overheating alarm gives an alarm condition value of 4+1=5.

2.3 Unload Condition​

Byte BitBIT7BIT6BIT5BIT4BIT3BIT2BIT1BIT0
Bit Weight1286432168421
Address 19----Load overload--Overcurrent protectionOverheating protectionMagnetic encoder protectionVoltage protection
 ----(0) Disable load overload--(0) Disable overcurrent protection(0) Disable overheating protection(0) Disable magnetic encoder protection(0) Disable voltage protection
----(1) Enable load overload--(1) Enable overcurrent protection(1) Enable overheating protection(1) Enable magnetic encoder protection(1) Enable voltage protection
info

If multiple bits are set at the same time, the servo's unload condition value is the sum of the individual bit values. For example: enabling both the voltage protection and the overheating protection gives an unload condition value of 4+1=5.

2.4 Servo Phase​

Byte BitBIT7BIT6BIT5BIT4BIT3BIT2BIT1BIT0
Bit Weight1286432168421
Address 18Position feedback direction phasePWM frequencyDriver bridge configurationAngle feedback modeSpeed modeSpeed unitDriver bridge modeDriver direction phase
(0) Forward(0) 24kHz(0) Independent H-bridge(0) Feedback single-turn angle(0) Speed 0 indicates stop(0) 0.732RPM(0) Brushless, effective after restart(0) Forward
(1) Reverse(1) 16kHz(1) Integrated H-bridge/no current feedback(1) Feedback full angle(1) Speed 0 indicates maximum speed(1) 0.0146RPM(1) Brushed, effective after restart(1) Reverse
info

If multiple bits are set at the same time, the servo's phase value is the sum of the individual bit values. For example: with the original phase value at 0 and the servo running in reverse, the phase value is 128+1=129.