Development Protocol

Function Code Introduction​

Function CodeDescription
03Read Holding Registers
04Read Input Registers
06Write Single Holding Register
10Write Multiple Holding Registers

Modbus Data Types​

The Modbus protocol defines 4 types of data areas, usually represented by 0x, 1x, 3x, and 4x for different address types.

Address TypeAddress RangeBasic Storage UnitRead/Write AttributeFunction Code
Coils0x0000-0xFFFF1 bitRead/Write01H, 05H, 0FH
Discrete Inputs1x0000-1xFFFF1 bitRead-only02H
Input Registers3x0000-3xFFFF16 bit / RegisterRead-only04H
Holding Registers4x0000-4xFFFF16 bit / RegisterRead/Write03H, 06H, 10H

The above is the standard Modbus data type classification. A device does not necessarily implement all 4 data areas at the same time, nor does it necessarily support all the function codes listed in the table.

Additional Notes on Register-Type Data

In Modbus, the basic width of each register is 16 bit. Actual data can occupy one or more consecutive registers:

  • 16-bit data: occupies 1 register
  • 32 bit data: occupies 2 consecutive registers

For example, 32-bit big-endian data 0x12345678:

RegisterData
Register N0x1234
Register N + 10x5678

That is, the byte order is 12 34 56 78.

The specific data length, data type, and byte order / word order of multi-register data should be based on the register description of the corresponding device.

Register Address Description​

Address (HEX)Register ContentRegister ValueAccessModbus Function Code
3x0000
3x0001
Channel 1 Frequency High 16 bits
Channel 1 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x0002Channel 1 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x0003
3x0004
Channel 2 Frequency High 16 bits
Channel 2 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x0005Channel 2 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x0006
3x0007
Channel 3 Frequency High 16 bits
Channel 3 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x0008Channel 3 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x0009
3x000A
Channel 4 Frequency High 16 bits
Channel 4 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x000BChannel 4 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x000C
3x000D
Channel 5 Frequency High 16 bits
Channel 5 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x000EChannel 5 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x000F
3x0010
Channel 6 Frequency High 16 bits
Channel 6 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x0011Channel 6 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x0012
3x0013
Channel 7 Frequency High 16 bits
Channel 7 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x0014Channel 7 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
3x0015
3x0016
Channel 8 Frequency High 16 bits
Channel 8 Frequency Low 16 bits
Unsigned 32‑bit value, unit 0.01 Hz, range: 40000 - 5000000, i.e., 400 Hz - 50 kHzRead0x04
3x0017Channel 8 Duty CycleValue is unsigned 16-bit hexadecimal, unit 0.01%, range 0-10000, i.e., 0-100%Read0x04
4x2000Serial Port ParametersHigh byte: parity mode: 0x00-0x02
Low byte: baud rate mode: 0x00-0x07
Read/Write0x03, 0x06
4x4000Device AddressStores Modbus address directly
Device address: 0x0001-0x00FF
Read/Write0x03, 0x06
4x8000Software VersionConvert to decimal, then shift decimal point two places left for version
0x0064 = 100 = V1.00
Read0x03

Command Operation Introduction​

Read Pulse Input Command​

Send: 01 04 00 00 00 03 B0 0B

FieldDescriptionNote
01Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0404 CommandRead Input Registers
00 00Register Start AddressStarting register for channel read. Each channel occupies three registers: first two store frequency, last stores duty cycle
00 03Number of RegistersNumber of registers to read, cannot exceed maximum register count
B0 0BCRC16CRC16 checksum of the first 6 bytes of data

Return Code: 01 04 06 00 3B 83 A5 03 01 7D C1

FieldDescriptionNote
01Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0404 CommandRead Input Registers
06Byte CountData length
3B 83
A5 03
03 01
Register Data
Frequency High 16-bit
Frequency Low 16-bit
Duty Cycle
Each channel occupies three registers: first two store frequency, last stores duty cycle
Frequency is unsigned 32-bit hexadecimal, unit 0.01 Hz, range: 40000-5000000 (400 Hz - 50 kHz)
Duty cycle: unsigned 16‑bit, unit 0.01%, range 0-10000 (0-100%)
7D C1CRC16CRC16 checksum of the first 6 bytes of data

Example: Device with address 1

Read channels 1-8 : 01 04 00 00 00 18 F0 00
Read channel 2 : 01 04 00 03 00 03 40 0B
Read channels 3-5 : 01 04 00 06 00 09 D0 0D
Read channel 1 : 01 04 00 00 00 03 B0 0B
Return: 01 04 06 00 00 9C 40 13 88 42 41 //Channel 1, 400 Hz, 50% duty cycle

Set Baud Rate Command​

Send Code: 00 06 20 00 00 05 43 D8

FieldDescriptionNotes
00Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0606 CommandSet baud rate, set device address
20 00Command Register0x2000 for setting baud rate, 0x4000 for setting device address
00Parity Mode0x00 for no parity, 0x01 for odd parity, 0x02 for even parity
05Baud Rate ValueBaud rate value mapping:
0x00: 4800
0x01: 9600
0x02: 19200
0x03: 38400
0x04: 57600
0x05: 115200
0x06: 128000
0x07: 256000
43 D8CRC16CRC16 checksum of the first 6 bytes of data

Return Code: 00 06 20 00 00 05 43 D8

FieldDescriptionNotes
00Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0606 CommandSet baud rate, set device address
20 00Command Register0x2000 for setting baud rate, 0x4000 for setting device address
00Parity Mode0x00 for no parity, 0x01 for odd parity, 0x02 for even parity
05Baud RateBaud rate value mapping:
0x00: 4800
0x01: 9600
0x02: 19200
0x03: 38400
0x04: 57600
0x05: 115200
0x06: 128000
0x07: 256000
43 D8CRC16CRC16 checksum of the first 6 bytes of data

Example: Device with address 1

Set baud rate 4800 : 00 06 20 00 00 00 83 DB
Set baud rate 9600 : 00 06 20 00 00 01 42 1B
Set baud rate 115200 : 00 06 20 00 00 05 43 D8

Set Device Address Command​

Send Code: 00 06 40 00 00 01 5C 1B

FieldDescriptionNotes
00Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0606 CommandSet baud rate, set device address
40 00Command Register0x2000 for setting baud rate, 0x4000 for setting device address
00 01Device AddressDevice address set, 0x0001-0x00FF
5C 1BCRC16CRC16 checksum of the first 6 bytes of data

Return Code: 00 06 40 00 00 01 5C 1B

FieldDescriptionNotes
00Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0606 CommandSet baud rate, set device address
40 00Command Register0x2000 for setting baud rate, 0x4000 for setting device address
00 01Device AddressDevice address set, 0x0001-0x00FF
5C 1BCRC16CRC16 checksum of the first 6 bytes of data

Example: Device with address 1

Set device address to 0x01 : 00 06 40 00 00 01 5C 1B
Set device address to 0x02 : 00 06 40 00 00 02 1C 1A
Set device address to 0x03 : 00 06 40 00 00 03 DD DA

Read Device Address Command​

Send code: 00 03 40 00 00 01 90 1B

FieldDescriptionNotes
00Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0303 CommandRead device address command
40 00Command Register0x4000 for reading device address, 0x8000 for reading software version
00 01Byte CountFixed 0x0001
90 1BCRC16CRC16 checksum of the first 6 bytes of data

Return code: 01 03 02 00 01 79 84

FieldDescriptionNotes
01Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0303 CommandRead software version, read device address command
02Byte CountReturned byte count
00 01Device AddressDevice address set, 0x0001-0x00FF
79 84CRC16CRC16 checksum of the first 6 bytes of data

Example: Device with address 2

Send Code: 00 03 40 00 00 01 90 1B
Return code : 02 03 02 00 02 7D 85 //Address 0x02

Read Software Version Command​

Send Code: 00 03 80 00 00 01 AC 1B

FieldDescriptionNotes
00Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0303 CommandRead software version, read device address command
80 00Command Register0x4000 for reading device address, 0x8000 for reading software version
00 01Byte CountFixed 0x0001
AC 1BCRC16CRC16 checksum of the first 6 bytes of data

Return Code: 01 03 02 00 64 B9 AF

FieldDescriptionNotes
01Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
0303 CommandRead software version, read device address command
02Byte CountReturned byte count
00 64Software VersionConvert to decimal, then shift decimal point two places left for version
0x0064 = 100 = V1.00
B9 AFCRC16CRC16 checksum of the first 6 bytes of data

Example: Device with address 1

Send Code: 00 03 80 00 00 01 AC 1B
Return Code: 01 03 02 00 64 B9 AF //0x0064 = 100 =V1.00

Exception Function Codes​

If the received command is incorrect or an exception occurs, the device will return an exception response. The exception response format is as follows:

Return Code: 01 85 03 02 91

FieldDescriptionNotes
01Device Address0x00 indicates broadcast address; 0x01-0xFF indicate device address
85Exception Function CodeException function code = Request function code + 0x80
03Byte CountException code
02 91CRC16CRC16 checksum of the first 6 bytes of data

The exception code is a single-byte value indicating the type of error. Several common exception codes defined by the Modbus protocol:

Exception CodeNameDescription
0x01Illegal FunctionThe requested function code is not supported
0x02Illegal Data AddressThe requested data address is incorrect
0x03Illegal Data ValueThe requested data value or operation cannot be performed
0x04Server FailureServer device failure
0x05AcknowledgeRequest received and processing
0x06Device BusyDevice is busy and cannot execute the requested operation